High Voltage Outdoor Cutout Fuse 12kV DNK
In addition to the function as a fuse used in power distribution system the SSOC (NCF)3 fuse can be also applied as the outdoor load switch equipped with an independent arcing chute for loadbreak which restricts the electrical arc and provides de-dissociation function.
HIGH QUALITY MATERIALFuse tube - epoxy fiber glass with fiber lining coated with special ultraviolet resistant material, the corresponding disconnect switch knife can be here selected.
2. Upper contact - silver to silver, high contact pressure squeezed by stainless steel spring.
3. Trunnion - high strength cast copper, silver - plated, and pressed on the side surface of the hinge around the trunnion surface to ensure the fuse tube alignment while switching-on.
TECHNICAL PARAMETER:Max. operation voltage: 12kVRated continuous operation current: 100A/200ARated frequency: 50HzFuse base rated current: 100A/200ARated short-circuit breaking current: 12.5kA/100A (4time) 12.5kA/200A (1time)AC voltage withstand (wet): 50kVAC voltage withstand (dry): 60kVRated lightning impulse voltage withstand: 12kV/150kVCreepage-distance : 32.3mm/kVMechanical life: 500 times of continuous switch-off and switch-onElevation: 2000mAmbient temperature: -40°c+70°cOUTLINE DRAWING DIMENSION:
INSTALLATION HOLDER DIMENSIONS:STANDRAD:
The design and test of SSOC (NCF) fuse accords with requirments of the following standards:
IEC282.1 IEC787ANSI C37.41-94 ANSI C37.42-94GB 15166.3-2008 GB311.1-97DL/T 640-97 DL/T 593-96High Voltage Outdoor Cutout Fuse 12kV DNK